Permit Information
Permit NumberFIR04-00564
StatusFinaled
Name DE BEST FIRE PROTECTION
Site Address 1379 N CLOVERDALE RD
Project NameSPR UG TUMBLE TIME GYMNASTICS
Customer Number 
ePlanReview 
Description
TUMBLE TIME GYMNASTICS * To install a single service fire sprinkler supply main into a new 12,554-ft/2, Type VB, two story pre-engineered fully fire sprinklered gymnastics facility. Fire sprinklers are used for area and story increase. The supply will be 6" C-900 connecting at the property line off the west side of Cloverdale, running approximately 83'-0" to a M.J. 90, then north approximately 12'-0" and up through the finish floor approximately 1'-0" with an 6" Ames SS Ready Riser with a grooved connection. The fire sprinkler underground work shall comply with NFPA 13-2002, NFPA 24-2002 the IFC-2000, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum fire code. This permit is attached to building permit: BLD04-00888.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/21/20051/21/20051/21/2005PPASS
DetailsTroy Cobbley
Underground finaled
INSP-Supply line flush12/13/200412/14/200412/14/2004APASS
DetailsTroy Cobbley
Underground supply piping flushed 12/14/2004 8:32:42 AM
INSP-Sprinkler Rough-in9/29/20049/30/20049/30/2004APART
DetailsTroy Cobbley
6" C900 has been installed but layout does not match plan. Piping is ok to cover but resubmittals are required prior to final approval on this permit. Also show revised layout for the overhead piping plans. 9/30/2004 12:36:08 PM