Permit Number | FIR04-00564 |
Status | Finaled |
Name |
DE BEST FIRE PROTECTION
|
Site Address |
1379 N CLOVERDALE RD
|
Project Name | SPR UG TUMBLE TIME GYMNASTICS |
Customer Number | |
ePlanReview | |
Description |
TUMBLE TIME GYMNASTICS * To install a single service fire sprinkler supply main into a new 12,554-ft/2, Type VB, two story pre-engineered fully fire sprinklered gymnastics facility. Fire sprinklers are used for area and story increase. The supply will be 6" C-900 connecting at the property line off the west side of Cloverdale, running approximately 83'-0" to a M.J. 90, then north approximately 12'-0" and up through the finish floor approximately 1'-0" with an 6" Ames SS Ready Riser with a grooved connection. The fire sprinkler underground work shall comply with NFPA 13-2002, NFPA 24-2002 the IFC-2000, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum fire code. This permit is attached to building permit: BLD04-00888.
|