Permit Information
Permit NumberFIR04-00617
StatusFinaled
Name PEAK ALARM
Site Address 9288 W EMERALD ST
Project Namealm - GE HARRIS LLC
Customer Number 
ePlanReview 
Description
To replace an existing fire alarm system. The required sprinkler monitoring fire alarm system includes HVAC shutdown (all units in the building are being connected at this time, the duct detectors are existing) and notification throughout the remodeled area of the TI only.

10/21/2004 - Additional scope: The front door will have magnetic locks, therefore the fire alarm system is designed to "release" the locks in case of alarm. This door must also comply with IFC 1003.3.1.3.4, Access-controlled egress doors. Plans show four (4) exterior doors, only the front has magnetic locks.

The associated building permit (BLD 04-01723) is to remodel an existing tenant space. Work will include, adding walls to reduce the size of this tenant space from 20674 sq ft to 11,319 sq ft, installation of new janitors sink, minor remodel of restrooms to make more accessible, modify entrance. This building is fully fire sprinklered any alterations to the sprinkler system shall be per NFPA #13 as regulated by the fire department. (pc#482-04) rmh (GE HARRIS LLC-STELLAR SYNAMIC DIVISION)

Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/1/20052/1/20052/1/2005PPASS
DetailsRick Jackson
3 duct detectors weren't required as the untos weren't there; all items tested okay - only wall PIV is the only tamper 2/1/2005 2:18:42 PM
INSP-Alarm Testing12/17/200412/20/200412/20/2004PFAIL
DetailsTroy Cobbley
Ran out time to finish inspection. Phone lines tested ok. No other items tested. 12 volt side of the panel needs 12 amp hour battery. Did not test the 24 volt side. 24 volt side does not supervise both batteries per nfpa 72. 12/20/2004 4:08:18 PM