Permit Information
Permit NumberFIR04-00655
StatusFinaled
Name ALARMCO
Site Address 777 N FIVE MILE RD
Project Namealm - Consolidated Supply
Customer Number 
ePlanReview 
Description
To replace a required sprinkler monitoring fire alarm system. 4/19/2005 that includes HVAC shutdown.

There is no associated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/23/201012/23/201012/23/2010PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection12/23/201012/23/201012/23/2010PPASS
DetailsTroy Cobbley
Permit finaled
FIR-Aging Inspection12/23/201012/23/201012/23/2010 PASS
DetailsTroy Cobbley
Permit finaled
FIR-Aging Inspection10/14/201010/14/201010/20/2010 DONE
DetailsTroy Cobbley
I spoke to Greg Jackson, the branch manager for Consolidated Supply, about the pressure switch requirement for the dry pipe valve.
INSP-Final Inspection7/12/20107/12/20107/14/2010PFAIL
DetailsTroy Cobbley
The duct smoke detector was mounted incorrectly so it was not tested. The missing high/low pressure switch will be handled by prevention. If not included on this permit as an as-built a separate permit will be required when it is added to the existing fire alarm system.
INSP-Final Inspection7/9/20107/12/20107/12/2010ACANC
DetailsTroy Cobbley
Duplicate inspection
INSP-Final Inspection7/8/20107/9/20107/9/2010ACANC
DetailsTroy Cobbley
to be rescheduled
INSP-Conference6/16/20107/6/20107/6/2010ADONE
DetailsTroy Cobbley
Per Bill this will be called in within the next day or two.
INSP-Final Inspection6/23/20106/24/20106/25/2010AFAIL
DetailsForrest France
Re-inspection for correction items dated 2/7/05. Items still not repaired include; provide high/low air pressure switch monitoring, map at the FACP, signage at the riser door, battery trouble did not report. Items retested okay include sprinkler waterflow and phone line 2. Noted one duct detector has been installed and NFPA 72 forms were on site.
INSP-Sprinkler Rough-in/Hydro6/21/20106/22/20106/22/2010ACANC
DetailsForrest France
Incorrect inspection type request.
INSP-Conference6/10/20106/15/20106/16/2010ADONE
DetailsTroy Cobbley
I spoke to Greg Jackson, the branch manager, for Consolidated Supply about the need to get this permit finaled. He placed a phone call to Bill at Alarmco. I was handed the phone and Bill stated that he would have a tech out there tomorrow and hopefully an inspection called in for Friday. A follow up inspection has been scheduled.
INSP-Conference6/3/20106/10/20106/10/2010ADONE
DetailsTroy Cobbley
Bill has not been able to sent a tech out yet. He will try again. Follow up inspection set up for next week.
FIR-Aging Inspection6/2/20106/2/20106/3/2010 NR
DetailsTroy Cobbley
Per Lorie a tech is being sent out to check project status. I will be notified within the next day or two. A follow up inspection has been scheduled for next week.
FIR-Aging Inspection3/18/20103/18/20103/24/2010 NR
DetailsTroy Cobbley
Permit information forwarded to Stephanie and to Scott for further action.
INSP-Final Inspection2/4/20052/7/20052/7/2005AFAIL
DetailsTroy Cobbley
Provide verification duct smoke detectors are not required. Provide high/low pressure switch monitoring. Test waterflow. Provide map at facp. Not receiving phone line 2 trouble or the battery troubles. Provide signage for the riser door. Provide nfpa 72 forms 2/7/2005 11:37:06 AM
FIR-Aging Inspection2/1/20052/1/20052/1/2005 NR
DetailsTroy Cobbley
Per Terri they are waiting for the knox key box to be installed and then will call in the final. 2/2/2005 3:45:09 PM