Permit Information
Permit NumberFIR04-00679
StatusFinaled
Name FIRE SERVICE OF IDAHO
Site Address 10496 W OVERLAND RD
Project NameJACK IN THE BOX
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/6/200412/6/200412/6/2004PPASS
DetailsTroy Cobbley
Hood suppression system operated correctly
INSP-Final Inspection12/6/200412/6/200412/6/2004PPASS
DetailsTroy Cobbley
Hood suppression system operated correctly
INSP-Final Inspection12/2/200412/3/200412/3/2004AFAIL
DetailsTroy Cobbley
nozzles exceed 16" from centerline of the hazard and exceed the 40"-48" from the cooking surface. No test performed. 12/3/2004 8:52:33 AM
INSP-Sprinkler Rough-in/Hydro12/3/200412/3/200412/3/2004PFAIL
DetailsTroy Cobbley
Need air balance report for hood 12/3/2004 2:37:02 PM
INSP-Final Inspection11/29/200411/30/200411/30/2004ACANC
DetailsTroy Cobbley
hank; Phone #: ###-#### Internet Inspection Request from: Barbara Moore. Cancelled by Hank. Hood not ready for inspection 11/30/2004 12:42:31 PM