Permit Information
Permit NumberFIR04-00682
StatusFinaled
Name ALARMCO
Site Address 10095 W EMERALD ST
Project NamealmEmerald Tech Center Bld. 10
Customer Number 
ePlanReview 
Description
To provide a required sprinkler monitoring fire alarm system that includes HVAC shutdown.

FIR04-00682 is associated with building permit BLD 04-00871. These two permits must be completed prior to finalizing FIR04-00654. The building permit is to construct a new 11,504 square foot, one story, concrete tilt-up office and warehouse shell building and related site improvements. This is a shell permit only and no occupancy is allowed under this permit. A separate tenant improvement permit is required to finish this building for occupancy. All construction per the approved plans and attached comment list. This building is fully fire sprinklered. DRH04-00031/PC# 245-04/JCM Emerald Tech Center Building #10 (Shell Only) -

The associated building permit (BLD 04-01918) is to construct a 10,752 square foot office tenant space located within an existing 10,944 square foot building. The building shell was constructed under permit BLD04-00871. Work is to include interior nonbearing walls, 2 restrooms accessible to the disabled, interior doors, suspended ceilings, and finishes all per the approved drawings and the plan review report on file. The fire sprinkler system shall comply with NFPA 13-2002 as regulated by the Fire Department. **CJW** (N.O.A.A. - EMERALD TECH CENTER - BLDG #10) This building is fire sprinklered.

Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/17/200411/17/200411/17/2004APASS
DetailsTroy Cobbley
Fire alarm finaled
INSP-Final Inspection11/16/200411/16/200411/16/2004PCANC
DetailsTroy Cobbley
To be rescheduled 11/16/2004 3:38:24 PM
INSP-Final Inspection11/16/200411/16/200411/16/2004AFAIL
DetailsTroy Cobbley
Duct detectors did not shut down hvac unit immediately. Monitoring station did not receive supervisory signals