INSP-Final Inspection | 9/16/2005 | 9/20/2005 | 9/20/2005 | A | PASS |
Forrest France
|
|
|
Fire sprinkler passed inspection, permit finaled.
|
INSP-Final Inspection | 9/14/2005 | 9/15/2005 | 9/16/2005 | A | PART |
Forrest France
|
|
|
Okay for final, however, the main control valves are shut at this time.
|
INSP-Final Inspection | 9/13/2005 | 9/14/2005 | 9/14/2005 | A | FAIL |
Forrest France
|
|
|
Heads in the mud room do not match temp. ratings, one is 155 and one is 175 degree, provide hydraulic calc. sticker at riser. Note of concern, the combined domestic and fire supply line flush prior to connection at the sprinkler riser was NOT witnessed or requested to be witnessed for verification by an inspector, the system has already been charged, contractor claims a flush was performed by the plumbers, contractor to assume responsibility for any possible contaminants in the system due to non-compliance.
|
INSP-Final Inspection | 9/12/2005 | 9/12/2005 | 9/12/2005 | P | NR |
Forrest France
|
|
|
Contractor called to cancel and reschedule for tomorrow 9/13, not ready today for inspection.
|
INSP-Supply line flush | 6/3/2005 | 6/6/2005 | 6/6/2005 | A | CANC |
Forrest France
|
|
|
Cancel inspection per Bruce with Commercial Fire protection.
|
INSP-Sprinkler Rough-in | 1/5/2005 | 1/6/2005 | 1/6/2005 | A | PART |
Rick Jackson
|
|
|
bruce; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Completed on 1/5/05 - okay to cover 1/6/2005 11:07:49 AM
|
INSP-Sprinkler Rough-in | 1/4/2005 | 1/5/2005 | 1/5/2005 | A | PART |
Rick Jackson
|
|
|
Bruce-call before you go; Phone #: ###-#### Internet Inspection Request from: Jan Rice Okay to cover - tenting completed; water meter not installed and riser not completed; heads not installed in all areas 1/5/2005 4:15:22 PM
|