Permit Information
Permit NumberFIR04-00800
StatusFinaled
Name JAMES GLANCEY
Site Address 2222 S COLE RD
Project Namealm - Fast Glass
Customer Number 
ePlanReview 
Description
To provide a required sprinkler monitoring fire alarm system that includes notification throughout.

FIR04-00769 is for the core and shell and is associated with this building permit. The associated building permit (BLD 04-02144) is to construct a new 11,500 square foot, one story, masonry and wood framed shell and core building. This building is fully fire sprinkled. This building will contain 5 future tenant spaces. Four of the proposed tenant space will have a vanilla finish and include one accessible restroom (lease spaces #106-#109). The remaining 5610 square foot tenant space will be finished for Fast Glass (BLD04-02145). This is a shell and core permit only and no occupancy is allowed under this permit. Separate tenant improvements permits will be required to finish each tenant space for occupancy. All construction per the approved plans and attached comment list. #04-599/JCM Lot #8, Airway Park Subdivision - (Shell & Core) *

FIR04-00800 is for the Fast Glass TI and is associated with this building permit. The associated building permit (BLD 04-02145) is to finish a 5,610 square foot tenant space for occupancy. This tenant space is located at the north half of the new 11,500 square foot Airway Court - Lot #8 shell and core building (BLD04-02144). This tenant space consists of a 425 square foot office area, two handicapped accessible restrooms and a 5,060 square foot warehouse area. All construction per the approved plans and attached comment list. JCM Fast Glass Tenant Improvement
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/6/20054/6/20054/6/2005PPASS
DetailsForrest France
Fire alarm finaled
INSP-Final Inspection3/30/20053/30/20053/30/2005PFAIL
DetailsTroy Cobbley
Racks are blocking visuals. Need to resubmit accounting for obstructions to strobe coverage. 3/30/2005 1:01:00 PM