Permit Information
Permit NumberFIR05-00039
StatusFinaled
Name DE BEST FIRE PROTECTION
Site Address 301 S CAPITOL BLVD
Project NameBODO BUILDING 7 UG SPR
Customer Number 
ePlanReview 
Description
BODO - BUILDING #7 (SHELL-UG) - To install 6" C-900 PVC from approximately39'-0" out from the south side of the building, located off Broad Street, running north under the footing and up through the finished floor with 6" Ductile Iron approximately 6" with a M.J. x Flange adapter, of a fire sprinkler control room. This service is the underground fire service supply for a new 135,950-ft/2 multi-plex theater, offices, retail and restaurant tenants. The fire sprinkler system is being used for area increase. This is a shell permit only and no occupancy is allowed under this permit. This is an underground fire permit only. The fire sprinkler underground work shall comply with NFPA 13-2002, NFPA 24-2002 the IFC-2000, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum fire code. This permit is attached to building permit: BLD04-01324.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/8/200511/9/200511/9/2005APASS
DetailsForrest France
UG fire supply line permit finaled.
INSP-Final Inspection11/1/200511/1/200511/1/2005PPASS
DetailsForrest France
Underground supply finaled.
INSP-Supply line flush9/23/20059/26/20059/26/2005PPART
DetailsForrest France
Underground fire supply line flush is satisfactory, pitot reading measured 24 psi. at 4" opening under full flow condition.
INSP-Sprinkler Rough-in/Hydro4/22/20054/22/20054/22/2005PPART
DetailsForrest France
Fire supply UG stub out good for cover, will require as-built for additional 90 okayed by Bill A. per Jim Danes.