Permit Information
Permit NumberFIR05-00045
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 3101 W MAIN ST
Project NameSPR RIVERFRONT PLAZA LLC
Customer Number 
ePlanReview 
Description
RIVERFRONT PLAZA-OFFICE BUILDING SHELL & CORE - To install the underground supply and the complete fire sprinkler (shell & core) system for Light Hazard Occupancy in a 21,680-ft/2, two story, office shell and core building. The core work to be completed under this permit include the stairways, elevator and machine room, first floor lobby, restrooms and electrical room and second floor lobby, restrooms and nonrated corridor. This building is constructed concrete tilt-up exterior wall, and steel structural frame with steel floor joists and roof trusses. This building is fully fire sprinklered. First Floor is: 11,120-ft/2, and the second Floor is: 10,560-ft/2. All construction per the approved plans and attached comment list. The fire sprinkler system work shall comply with the IFC 2000, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD04-00045.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/13/20057/14/20057/14/2005PPASS
DetailsForrest France
Fire sprinkler finaled.
INSP-Final Inspection7/8/20057/8/20057/8/2005PPART
DetailsForrest France
Need ceiling tile installed at head locations and escutcheons on prior to final, provide NFPA 25, provide signs for auxillary drains.
INSP-Final Inspection7/6/20057/7/20057/7/2005AFAIL
DetailsForrest France
Repair outside bell, perform forward flow test, provide heads, head wrench, and NFPA 25 in head box, provide sinage on all valves in riser room, install ceiling tile and canopies prior to final.
INSP-Final Inspection7/1/20057/1/20057/1/2005PPART
DetailsForrest France
Overhead hydro test passed, rough-in is good for cover. Need alarms and forward flow tesing prior to final.
INSP-Sprinkler Rough-in/Hydro6/24/20056/27/20056/27/2005PFAIL
DetailsForrest France
Attatch retaining strap at hanger first floor nw corner, provide flexible coupling at 4" main where it passes through floor slab, provide retaining nuts on sammy screws at 2nd floor trapeze hangers, provide plans showing upright heads above exterior canopy west side, upright heads at some locations in shell areas 1st and 2nd floors are blocked by truss webs, TI demising walls, and plumbing pipe.
INSP-Supply line flush6/14/20056/16/20056/16/2005APART
DetailsForrest France
Underground fire supply line hydro and flush both passed inspection.
INSP-Sprinkler Rough-in5/19/20055/20/20055/20/2005ACANC
DetailsForrest France
Cancel inspection per. Tom Easton at Grinnell. Duplicate inspection, this inspection already completed the previous day.
INSP-Conference5/19/20055/19/20055/19/2005PDONE
DetailsForrest France
On site discussion with Tom Easton of Grinnell regarding sprinkler coverage requirements in concealled spaces above awning. Spoke with Bill Alexander regarding this issue and concluded sprinklers are required.
INSP-Sprinkler Rough-in5/19/20055/19/20055/19/2005PCANC
DetailsForrest France
please call 30 min prior to inspection//tom; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa///cancel per tom easton 5/19/05 12:20pm BAS
INSP-Sprinkler Rough-in5/19/20055/19/20055/19/2005PPART
DetailsForrest France
Underground fire supply line stub out OK to cover.
INSP-Sprinkler Rough-in5/10/20055/11/20055/11/2005AFAIL
DetailsForrest France
Overhead pipe installed does not match piping plan on approved drawings in front entry or 2nd floor main/branch line connections. Re-submit plans reflecting all field changes.
INSP-Sprinkler Rough-in/Hydro5/11/20055/11/20055/11/2005AFAIL
DetailsForrest France
Underground fire supply main does not meet min. 4'-6" depth of bury requirements. Provide sleeve for EQ clearance through floor slab at riser. Cover bolts at MJ 90.
INSP-Sprinkler Rough-in4/11/20054/11/20054/11/2005PFAIL
DetailsTroy Cobbley
Could not find plans to do the inspection
INSP-Sprinkler Rough-in4/7/20054/8/2005 A 
Details
mick Note: cover underground; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles