Permit Information
Permit NumberFIR05-00062
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 3110 S BOWN WAY
Project NameSPR KESSLER'S CAFE
Customer Number 
ePlanReview 
Description
(KESSLER'S RESTAURANT)(BOWN CROSSING MARKET PLACE-BLDG 'B'-1ST FLR) To add new pendant fire sprinkler protection in a new 2,308-ft/2 restaurant tenant on the entire first floor of an existing shell & core space (BLD03-02190/FIR04-00265). The fire sprinkler work is related to the construction of new interior walls to create a kitchen / food prep area, walk in cooler and suspended ceiling grid system in kitchen/scullery. Also the requirement to relocate an existing 2½" main and an 1¼" branchline on the 3rd floor for type 1 hood duckwork. This fire protection work shall comply with the IFC 2003 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD04-02505.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/6/20057/6/20057/6/2005APASS
DetailsForrest France
Fire sprinkler finaled.
INSP-Final Inspection7/1/20057/1/20057/1/2005PPART
DetailsForrest France
Need to install two escutcheons on heads in the kitchen area.
INSP-Final Inspection6/13/20056/13/20056/13/2005PPART
DetailsForrest France
Remainder of rough-in at kitchen area OK to cover. Need ceiling tile installed at heads, foreward flow and alarms for final.
INSP-Final Inspection5/10/20055/11/20055/11/2005APART
DetailsForrest France
Rough-in above hard lid areas first floor cafe OK to cover. Grid ceiling and heads in grid ceiling areas not installed yet. Verify wood 2x4's above hard lid at south soffit are fire treated.
INSP-Sprinkler Rough-in/Hydro5/10/20055/10/20055/10/2005PFAIL
DetailsForrest France
Hanger on 1" arm over at end of 2" main, north side, is not within 2' of the end. Pendent head in soffit hard lid at corner is not installed as shown on plan. EQ brace on relocated 2 1/2" main is not installed on the last piece of main as shown on plan.
INSP-Sprinkler Rough-in/Hydro3/4/20053/7/20053/7/2005APASS
DetailsTroy Cobbley
Fire sprinklers ok to cover above hard lids 3/7/2005 9:06:40 AM