Permit Information
Permit NumberFIR05-00084
StatusFinaled
Name PROTEX
Site Address 420 W MAIN ST
Project Namealm - VELTEX BLDG-1ST FLR
Customer Number 
ePlanReview 
Description
To provide total notification to the newly remodeled area on the first floor. The required manual fire alarm system includes sprinkler monitoring, HVAC shutdown, fire/smoke damper control, door release and notification throughout.

The associated building permit (BLD 04-02978) is to finish approximately 5,494 sq.ft. of interior tenant space for a bank. Work to include relocation of existing front entry door and add a new exterior door at entry, install interior partition walls and cabinets, counter tops and bank vault. All construction per the approved plans and attached comment list. NOTE: This building is fully fire sprinklered for story increase. MJP - (STERLING SAVINGS BANK)(VELTEX BLDG-1ST FLR)
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/21/20054/21/20054/21/2005APASS
DetailsForrest France
Fire alarm finaled.
INSP-Alarm Testing4/15/20054/18/20054/18/2005AFAIL
DetailsForrest France
Fail inspection, in-duct detectors/dampers located in upper mechanical room failed to operate properly.
INSP-Conference3/7/20053/8/20053/8/2005PDONE
DetailsTroy Cobbley
nick///for box lacations; Phone #: ###-#### Internet Inspection Request from: Barbara Moore

Verified box locations, a H/S on northeast wall shifted, it could be a problem if the cubicle walls are greater than 6'. Nick stated that they are having to shift remote test switches for existing duct detectors. I told him to keep track of all FA changes and to resubmit a "plan modification" about a week prior to the final inspection.