Permit Number | FIR05-00085 |
Status | Finaled |
Name |
AUDIO ELECTRONICS INC
|
Site Address |
412 E PARKCENTER BLVD
|
Project Name | alm - Stor cast TI 2nd floor |
Customer Number | |
ePlanReview | |
Description |
5/12/2005 - Additional scope of work, to change existing core and shell notification appliances (6 ea) to System Sensor. To remove the two (2) horn/strobes located in the stairwells on the second floor. The battery calculations appear sufficient. No written comments. The PDS Fire Inspector shall field verify functionality of the affected NAC circuit.
To relocate a 75cd H/S (appliance was a ceiling mount, will be changed to a wall mount, spacing is acceptable based upon the performance calculation (45 feet for 75 cd)) to provide total area coverage in the remodeled area in the north end of the second floor. The riser indicates the existing initiating devices are being modified, yet they are not clouded on the plan. Provide appropriate information to the PDS Fire Inspector for field verification of any relocated or modified initiating devices at inspection. Battery and voltage drop calculations are acceptable. The associated building permit (BLD 04-02660) is to construct new interior non bearing walls to establish new offices at second story. Bi-level switching required to new offices. Lever hardware required to new door and relocated doors. Fully Fire Sprinklered building any modification of sprinkler heads and or alarm system will require a Fire Permit. Construction type IIIA 1 hour, Occupancy B, Occupant load 25, Floor load 50, floor sq. ft. 2,413. ALREADY PD FEES FOR WHOLE THING JUST NEED TO ISSUE PERMIT./MLS
|