Permit Information
Permit NumberFIR05-00107
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 101 S CAPITOL BLVD Unit: 1900
Project NameSPR US BANK-18/19/2TH FLRS
Customer Number 
ePlanReview 
Description
(US BANK - 5TH FLOOR ELEVATOR LOBBY AND RESTROOM UPGRADE) To add modified fire sprinkler protection to the elevator lobby and restrooms upgrade. Also to remove and replace all fire sprinklers on this floor to quick response fire sprinklers. This work is located on the 5th floor of an existing high-rise building. The area of the entire 5th story is about 14,520-ft/2. Fire sprinkler work relating to the lobby and restroom upgrades is from interior nonbearing walls and ceiling work. The fire sprinkler systems (and the infrastructure supporting the system) are regulated under the provisions of the 2000 IBC, which shall be upgraded throughout to comply with current code standards. This building is fire sprinklered because it is a high-rise. This fire protection work shall comply with the IFC 2003 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD04-02973.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/2/20056/2/20056/2/2005APASS
DetailsForrest France
Fire sprinkler finaled.
INSP-Final Inspection4/21/20054/22/20054/22/2005APART
DetailsForrest France
Overhead rough-in pass, need ceiling tile installed around pendent heads for final.
INSP-Sprinkler Rough-in/Hydro4/7/20054/7/20054/7/2005PPASS
DetailsForrest France
Elevator lobby only is ok to cover
INSP-Sprinkler Rough-in/Hydro3/11/20053/14/20053/14/2005APASS
DetailsTroy Cobbley
Hanger test in the elevator lobby passed. Bill found riser with outdated inspection tag. 3/14/2005 10:52:05 AM
INSP-Sprinkler Rough-in/Hydro3/7/20053/7/20053/7/2005PPART
DetailsTroy Cobbley
Sprinkler piping above the vaulted ceiling in the elevator lobby is ok to cover but will not be finaled until the revized piping size is approved. If piping is not approved all changes will be required to meet approval prior to finaling permit.
INSP-Sprinkler Rough-in3/3/20053/3/20053/3/2005 FAIL
DetailsTroy Cobbley
Inspection was for vaulted ceiling in the elevator lobby. The sprinkler piping on plans is 1 1/4" but piping is actually 1". Notified contractor that the piping laying on top of the soffits must meet nfpa 13 requirements for hanging. I could bent the soffit with my own weight. 3/3/2005 12:33:05 PM
INSP-Final Inspection4/19/20054/19/2005 P 
Details
mick; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles