Permit Information
Permit NumberFIR05-00110
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 3139 S BOWN WAY
Project NameSPR OH BOWN CROSSING-BLD G
Customer Number 
ePlanReview 
Description
(BOWN CROSSING MARKET PLACE-BLDG G) * To install fire sprinkler protection in a new 6,417-ft/2 two story, multi-tenant, shell building. The main floor will be protected for OH-2, "B" occupancy and the second floor will be protected for Light Hazard, "B" (Assembly). The first floor is 4,110-ft/2 and the second floor is 2,307-ft/2 with two exterior second floor decks at 300-ft/2 each. This building is fully fire sprinklered for Code reduction and allowable fire flow reduction. Separate permits, plans must be obtained and approved for each tenant space to be occupied. The fire sprinkler system work shall comply with the IFC 2000, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. The underground fire service supply was installed under FIR04-00082. This permit is attached to building permit: BLD03-02329.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/22/20056/23/20056/23/2005APASS
DetailsForrest France
Fire sprinkler passed inspections.
INSP-Sprinkler Rough-in/Hydro3/22/20053/22/20053/22/2005PPASS
DetailsTroy Cobbley
Above ground hydro test passed. Items on the correction notice have been corrected. 3/22/2005 3:39:30 PM
INSP-Final Inspection3/21/20053/21/20053/21/2005PFAIL
DetailsTroy Cobbley
Contact: ###-#### Overhead hydro fail. Rough in inspection okd ,except 2nd floor heads too far from deck, 2nd floor heads also need to be 200 degree per plan. Last hanger on end 1 1/4 branch lines must be within 48 in. 3/21/2005 2:47:15 PM