Permit Information
Permit NumberFIR05-00117
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 2895 S FEDERAL WAY
Project NameSPR JV GALLERY SUITE 102
Customer Number 
ePlanReview 
Description
(JV GALLERY - SUITE 102) To modify fire sprinklers in a shell building to create a 7,041-ft/2, 1st story tenant space comprising of 3,940-ft/2 showroom, 260-ft/2 office, 201-ft/ breakroom, 260-ft/2 restroom core and 2,380-ft/2 warehouse with interior tenant improvements. Fire sprinkler work is related to the addition of 2 restrooms, interior nonbearing walls, a new stairway to serve a future tenant on the 2nd floor and suspended ceilings. This building is fire sprinklered for area increase, story increase, and fire area. The fire sprinkler system shall comply with NFPA 13 as regulated by the Fire Department. This fire protection work shall comply with the IFC 2003 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD05-00259.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/9/20055/9/20055/9/2005PPASS
DetailsForrest France
Fire sprinkler finaled.
INSP-Sprinkler Rough-in4/20/20054/21/20054/21/2005PPASS
DetailsForrest France
Overhead fire sprinkler rough-in OK.
INSP-Sprinkler Rough-in4/14/20054/15/20054/15/2005AFAIL
DetailsForrest France
Sprinkler upright opposite entry 101 wall is not installed as shown on plan causing adjacent head to be overspaced. Two added uprights on sheet FP2 south side line do not meet minimum separation requirements.