INSP-Final Inspection | 7/19/2005 | 7/19/2005 | 7/19/2005 | P | PASS |
Troy Cobbley
|
|
|
Fire alarm finaled
|
INSP-Final Inspection | 7/15/2005 | 7/15/2005 | 7/15/2005 | P | CANC |
Troy Cobbley
|
|
|
Request for temp
|
INSP-Final Inspection | 7/14/2005 | 7/15/2005 | 7/15/2005 | P | CANC |
Troy Cobbley
|
|
|
Troy, Here we go again. Please let us know what time will work for you tomorrow. Thanks. Jason (###-####); Phone #: ###-#### Internet Inspection Request from: Jason Minnick Inspection cancelled from web by: Jason Minnick
|
INSP-Final Inspection | 7/14/2005 | 7/14/2005 | 7/14/2005 | P | CANC |
Troy Cobbley
|
|
|
Troy, We would like to schedule an inspection for late this afternoon if at all possible. Around 3:00 would work the best for us, but whatever you could work in would be acceptable. Please call me at ###-####, so that I can have everyone onsite as needed. Thankd Troy. Jason; Phone #: ###-#### Internet Inspection Request from: Jason Minnick Inspection cancelled from web by: Jason Minnick
|
INSP-Final Inspection | 7/11/2005 | 7/11/2005 | 7/12/2005 | P | FAIL |
Troy Cobbley
|
|
|
Provide filter in the duct detector located at hvac unit #34, provide signage on riser room door, provide knox key box, test elevator recall, provide delay for shunt trip, resubmit plans showing the new devices, provide print out of alarm signals, the alarm bell turns on and off when water is flowing, provide map at facp, monitoring company has wrong site address.
|
FIR-Aging Inspection | 6/28/2005 | 6/28/2005 | 6/28/2005 | | NR |
Troy Cobbley
|
|
|
work is in progress
|