Permit Information
Permit NumberFIR05-00177
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 11311 W CHINDEN BLVD
Project NameSPR HEWLETT-PACKARD U.G.
Customer Number 
ePlanReview 
Description
HEWLETT-PACKARD U.G. * To replace 2 existing defective Underground Post Indicator valves. One at the entrance to Building #1 (PIV#1) is a 8" system lead-in control and the Sectional (PIV 5-47) control valves on a fire service loop located near building #7 & 5, discovered during an NFPA 25 annual inspection. Each PIV is tampered. This underground fire protection service supply work shall comply with IFC 2003, NFPA 13-2002, NFPA 24-2002, the attached review comment and conditions list; all regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is not attached to any building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/12/20055/13/20055/13/2005APASS
DetailsTroy Cobbley
Fire sprinkler finaled. The tamper switches reported to HP security office.
INSP-Final Inspection5/9/20055/9/20055/9/2005PPART
DetailsForrest France
PIV #1 is OK to cover. Need to verify new tamper switch operation, valve cycled open and closed, and height of PIV above grade after bury.
INSP-Final Inspection4/8/20054/8/20054/8/2005PPART
DetailsTroy Cobbley
PIV #2 is ok to bury. Still need inspection for #1 before I can final