Permit Information
Permit NumberFIR05-00209
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 3201 W AIRPORT WAY
Project NameSPR CONCOURSE B EXTEND-REMODEL
Customer Number 
ePlanReview 
Description
(BOISE AIR TERMINAL - CONCOURSE B AND AIRCRAFT LOADING WALKWAY) To extend dry pipe fire sprinkler protection beneath the existing "Original Concourse B," and add wet pipe fire protection for the new entrance vestibule and support structure to serve a new aircraft loading walkway at "Original Concourse B." Also modify existing wet pipe fire sprinkler protection for the remodel of the interior of "Original Concourse B" and "Concourse B Extension", which includes the 4 existing restroom remodels. Both Concourse B buildings are fire sprinklered to substitute for 1-hr fire-resistance rated construction. The fire sprinkler systems shall comply with NFPA 13-2002 as regulated by the Fire Department. This fire protection work shall comply with the IFC 2003 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD04-02772.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Sprinkler Rough-in/Hydro8/3/20058/3/20058/3/2005PPART
DetailsForrest France
Overhead rough-in is acceptable to cover.
INSP-Final Inspection6/28/20056/29/20056/29/2005APART
DetailsTroy Cobbley
Dry pipe system under Concourse "B" passed. 57 seconds for trip time. Per Carl Westfall new code requirements do not require the fire proofing for separation just fire sprinklers.
INSP-Final Inspection6/27/20056/28/20056/28/2005PFAIL
DetailsTroy Cobbley
This inspection was for the sprinkler modifications on the dry system under Concourse B. Need to replace/repair fire proofing affected by hangers and eq bracing, provide hydrostatic test papers and trip test the dry system. Hydro test passed.
INSP-Sprinkler Rough-in/Hydro6/27/20056/28/20056/28/2005PPASS
DetailsTroy Cobbley
This inspection was for the sprinkler modifications on the dry system under Concourse B. Need to replace/repair fire proofing affected by hangers and eq bracing, provide hydrostatic test papers and trip test the dry system. Hydro test passed.
INSP-Final Inspection8/30/20058/31/2005 A 
DetailsForrest France
Scheduled by a contractor via Hello! on 8/30/2005 at 4:20:18 PM. Contact: ###-####.