Permit Information
Permit NumberFIR05-00210
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 10740 W FAIRVIEW AVE
Project Namealm - DESERET INDUSTRIES
Customer Number 
ePlanReview 
Description
To upgrade the existing fire alarm system. A manual fire alarm system is required throughout the building due to the M over 500 occupancy load. The required manual fire alarm system shall include manual pull stations (as shown on the plans) HVAC shutdown and notification (visual and audible) throughout.

The associated building permit (BLD 04-02767) is to perform INTERIOR REMODEL ONLY to selective portions of an existing 52,0252q ft building. ALL EXTERIOR WORK WILL BE DONE UNDER A SEPARATE PERMIT. Work will include demolition of existing partitions to expand the retail area of this building. Also will include construction of interior nonbearing partitions, installation of a suspended ceiling system. Installation of a breakroom sink and new janitors sink. This building is fully fire sprinklered for area increase, any alterations or modifications to the sprinkler system shall be per NFPA #13 as regulated by the fire department. (Rmh) **(Deseret Industries)**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/16/20104/19/20104/20/2010PPASS
DetailsTroy Cobbley
permit finaled
INSP-Alarm Testing11/28/200511/28/200511/28/2005PPASS
DetailsForrest France
c/n items are complete, fire alarm passed inspection.
INSP-Alarm Testing11/23/200511/23/200511/23/2005PCANC
DetailsTroy Cobbley
No time for inspection
INSP-Alarm Testing11/21/200511/22/200511/22/2005ACANC
DetailsTroy Cobbley
No time for inspection.
INSP-Alarm Testing11/15/200511/16/200511/16/2005AFAIL
DetailsTroy Cobbley
Sample tubes are incorrect. The holes in the tubes as installed are 10" apart. Per Mark at Silent Knight tech support the holes on the 2.5 should be 2" o. c. and the 5.0 and 10.0 should be 3" o.c.
INSP-Alarm Testing11/9/200511/10/200511/10/2005AFAIL
DetailsTroy Cobbley
Pull stations are mounted too high, duct smoke detectors do not shut down the units and the remote annunciators don't work. Several duct detectors are mounted incorrectly and the sample tubes are incorrectly orientated. The strobes in the coolers and freezers need the listed backboxes to be installed which is part number WBB from System Sensor.
INSP-Final Inspection11/8/200511/9/200511/9/2005AFAIL
DetailsTroy Cobbley
don; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
INSP-Alarm Testing11/8/200511/9/200511/9/2005ACANC
DetailsTroy Cobbley
don; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
INSP-Alarm Testing11/8/200511/8/200511/8/2005PFAIL
DetailsTroy Cobbley
a/v's need to have heights and cd ratings checked on all devices and then tested. Need to test all duct smoke detectors. Need to test fire sprinkler devices. The rolldown doors have been removed from the fire alarm system.
INSP-Alarm Testing10/10/200510/10/200510/10/2005PFAIL
DetailsTroy Cobbley
Fire alarm contractor and the electrical contractor where unable to provide a voltage meter to measure standby battery requirements and did not have a telephone butt set for verification that two phone lines had been provided. I stopped test. No items inspected.
INSP-Conference8/11/20058/11/20058/11/2005PDONE
DetailsTroy Cobbley
Per sam rogers a temp would be acceptable if the existing fire alarm system provided adequate sound levels in the remodeled area. All other life safety items would need to be provided prior to the temporary occupancy being given
FIR-Aging Inspection7/28/20057/28/20058/1/2005 NR
DetailsTroy Cobbley
I left a message on Ridgeway Mechanicals answering machine requesting status of job from John or Earl. Construction is still in progress at the job site.