INSP-Final Inspection | 4/16/2010 | 4/19/2010 | 4/20/2010 | P | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Alarm Testing | 11/28/2005 | 11/28/2005 | 11/28/2005 | P | PASS |
Forrest France
|
|
|
c/n items are complete, fire alarm passed inspection.
|
INSP-Alarm Testing | 11/23/2005 | 11/23/2005 | 11/23/2005 | P | CANC |
Troy Cobbley
|
|
|
No time for inspection
|
INSP-Alarm Testing | 11/21/2005 | 11/22/2005 | 11/22/2005 | A | CANC |
Troy Cobbley
|
|
|
No time for inspection.
|
INSP-Alarm Testing | 11/15/2005 | 11/16/2005 | 11/16/2005 | A | FAIL |
Troy Cobbley
|
|
|
Sample tubes are incorrect. The holes in the tubes as installed are 10" apart. Per Mark at Silent Knight tech support the holes on the 2.5 should be 2" o. c. and the 5.0 and 10.0 should be 3" o.c.
|
INSP-Alarm Testing | 11/9/2005 | 11/10/2005 | 11/10/2005 | A | FAIL |
Troy Cobbley
|
|
|
Pull stations are mounted too high, duct smoke detectors do not shut down the units and the remote annunciators don't work. Several duct detectors are mounted incorrectly and the sample tubes are incorrectly orientated. The strobes in the coolers and freezers need the listed backboxes to be installed which is part number WBB from System Sensor.
|
INSP-Final Inspection | 11/8/2005 | 11/9/2005 | 11/9/2005 | A | FAIL |
Troy Cobbley
|
|
|
don; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
INSP-Alarm Testing | 11/8/2005 | 11/9/2005 | 11/9/2005 | A | CANC |
Troy Cobbley
|
|
|
don; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
INSP-Alarm Testing | 11/8/2005 | 11/8/2005 | 11/8/2005 | P | FAIL |
Troy Cobbley
|
|
|
a/v's need to have heights and cd ratings checked on all devices and then tested. Need to test all duct smoke detectors. Need to test fire sprinkler devices. The rolldown doors have been removed from the fire alarm system.
|
INSP-Alarm Testing | 10/10/2005 | 10/10/2005 | 10/10/2005 | P | FAIL |
Troy Cobbley
|
|
|
Fire alarm contractor and the electrical contractor where unable to provide a voltage meter to measure standby battery requirements and did not have a telephone butt set for verification that two phone lines had been provided. I stopped test. No items inspected.
|
INSP-Conference | 8/11/2005 | 8/11/2005 | 8/11/2005 | P | DONE |
Troy Cobbley
|
|
|
Per sam rogers a temp would be acceptable if the existing fire alarm system provided adequate sound levels in the remodeled area. All other life safety items would need to be provided prior to the temporary occupancy being given
|
FIR-Aging Inspection | 7/28/2005 | 7/28/2005 | 8/1/2005 | | NR |
Troy Cobbley
|
|
|
I left a message on Ridgeway Mechanicals answering machine requesting status of job from John or Earl. Construction is still in progress at the job site.
|