Description |
To provide total visual coverage in the new pool enclosure, relocate one manual pull station and add a new manual pull station. The required manual fire alarm system includes sprinkler monitoring, required automatic detection, HVAC shutdown, fire/smoke damper control, door release, elevator recall/shutdown, cooking hood monitoring and notification throughout. No written comments. Battery and voltage drop calculations appear to be sufficient. No written comments. The PDS Fire Inspector to field verify appropriate visual coverage, synchronization (appears to be a glass wall between the visuals for the spa and the pool areas) and manual pull station addressing and functionality. Provide updated building map at inspection.
The associated building permit (BLD04-02967) is to add a 40' X 51', 2,040 sq.ft pool enclosure to the west side of the existing hotel suites, to remove an existing exterior door at the spa area and enlarge the exterior wall opening between the spa and pool area. Relocation of the non-rated pool equipment and storage enclosure building as per the approved plans. NOTE: This building is fully fire sprinklered for area increase. All construction per the approved plans and attached comment list. MJP DRH04-00444 CUP04-00016 Springhill Suites Marriott -
|