Permit Number | FIR05-00224 |
Status | Finaled |
Name |
HEWLETT-PACKARD FA
|
Site Address |
11311 W CHINDEN BLVD
|
Project Name | alm - HP#8-LOWER |
Customer Number | |
ePlanReview | |
Description |
To provide total visual coverage in the two new conference rooms. The required manual fire alarm system includes sprinkler monitoring, required automatic detection, HVAC shutdown, fire/smoke damper control and notification throughout. No written comments. Battery calculations appear to be sufficient based upon 4 hours, generator information and fuel agreement are in packet. The PDS Fire Inspector to field verify total visual coverage.
The associated building permit (BLD05-00750) is to remodel the interior of an existing 465 sq. ft. work area to allow construction of two private conference rooms of 95 sq. ft. each. Framing to be non-combustible, fire-resistive. To modify suspended ceiling grid system, electrical, mechanical, sprinkler and alarm systems as required to meet tenants needs and comply with current adopted codes. Scope of work does not increase area or occupant load as currently exists. Maintain current fire resistive materials for 2 hour fire rating at floor & structural elements as currently exists. (HEWLETT PACKARD BLDG #8-LOWER)(CONFERENCE ROOMS)
|