Permit Information
Permit NumberFIR05-00249
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 3852 N EAGLE RD
Project Namealm -BOISE 1ST CHURCH NAZARENE
Customer Number 
ePlanReview 
Description
To provide required automatic detection (total coverage) and notification for an office remodeled space. The existing fire alarm system includes sprinkler monitoring, HVAC shutdown, fire/smoke damper control, door release, elevator recall/shutdown, cooking hood monitoring and notification throughout. The Family Life center is not required to have automatic detection and has required voice/evac.

The associated building permit (BLD 05-00222) is to remodel office space within an existing space. Work includes minor demolition of non-bearing partitions, new non-bearing partitions to create new offices and breakroom per approved plans. Fire Sprinklers are regulated by the Fire Dept. and NFPA 13. Boise First Church of Nazarene

Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/9/20056/10/20056/10/2005APASS
DetailsTroy Cobbley
Fire alarm finaled
INSP-Final Inspection6/2/20056/3/20056/3/2005PFAIL
DetailsTroy Cobbley
Need to install the 15cd strobe outside of the records room as shown on the approved plans and retest the notification circuit.