Permit Information
Permit NumberFIR05-00316
StatusFinaled
Name ALLIED GENERAL FIRE & SECURITY
Site Address 460 N MILWAUKEE AVE
Project NameSears
Customer Number 
ePlanReview 
Description
To complete the replacement of the fire alarm system that was started under FIR01-00584. The required manual fire alarm system includes sprinkler monitoring, HVAC shutdown, elevator control, fire/smoke damper control and smoke detectors located in beam pockets above garment racks.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/8/20063/14/20063/14/2006APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection12/22/200512/22/200512/22/2005PFAIL
DetailsTroy Cobbley
Need to test recall for elevator, flow switches need readjusted on the east and west systems, test duct detectors, change signals to 4/2 format, finish reviewing notes.
INSP-Final Inspection10/7/200510/10/200510/10/2005AFAIL
DetailsTroy Cobbley
Only tested the phone lines and three tamper switches. Phone lines had to be repaired as I waited. A meter had to be found for testing batteries but it didn't work. The supervisory points received at the central station do not match plans. Need to test all devices. Need security to the outlet on same circuti to the facp.
INSP-Final Inspection10/7/200510/7/200510/7/2005PCANC
DetailsForrest France
Inspection to be rescheduled for monday the 10th per agreement with Rick Jackson. Sufficient information to determine what has and has not been tested is not available to a degree that is comfortable for verification without being familiar with the project history. This inspection to be defered to Troy Cobbley per request by Forrest.
FIR-Aging Inspection10/4/200510/4/200510/6/2005 NR
DetailsTroy Cobbley
Per Rick Jackson work is in progress.