INSP-Final Inspection | 6/28/2006 | 6/28/2006 | 6/28/2006 | P | PASS |
Forrest France
|
|
|
Final inspection is satisfactory, record of completion forms not available at the time of inspection, contractor to provide at next meeting, permit finaled.
|
INSP-Alarm Testing | 2/28/2006 | 3/3/2006 | 3/3/2006 | A | PART |
Forrest France
|
|
|
Indicate added av in the office on 11th floor on as builts, 9th floor is missing notification in the confrence room and short hall, verify cd and dB in the server room on 9th, "server" room is now a break room on the 8th, show deleted av in the storage room on 7th, add av in the confrence room on 6th, delete high partition or add visual coverage at common area on 6th, adjust door closures at south end on 5th floor, show all required changes on approved plans for verification at next inspection.
|
INSP-Sprinkler Rough-in/Hydro | 2/13/2006 | 2/16/2006 | 2/16/2006 | A | CANC |
Forrest France
|
|
|
WOULD LIKE IT AT 8AM IF POSSIBLE. LET ME KNOW.. Internet Inspection Request from: Rick Groom Inspection cancelled from web by: Rick Groom
|
INSP-Alarm Testing | 2/6/2006 | 2/9/2006 | 2/8/2006 | A | CANC |
Troy Cobbley
|
|
|
WOULD LIKE TO DO THIS AT 8AM IF POSSIBLE.
IF NOT LET ME KNOW Internet Inspection Request from: Rick Groom Inspection cancelled from web by: Rick Groom
|
INSP-Alarm Testing | 1/24/2006 | 1/25/2006 | 1/25/2006 | A | PART |
Forrest France
|
|
|
Tested functionality of notification and voice evac devices on floors 11,9,7,6,5,4, and basement levels, tested pulls, smokes, DD, sprinkler tampers, door release, and nac batteries on the basement and 4th floors. Door closure sequence at 4th floor and threshold hang up in the basement repaired while on site, need to provide updated map at the panel, provide resubmittals reflecting all field changes in the basement (Angels). An additional inspection(s) will be required to complete testing for the remainder of items not tested today due to time constraints per agreement.
|
INSP-Alarm Testing | 1/11/2006 | 1/18/2006 | 1/11/2006 | A | CANC |
Forrest France
|
|
|
Internet Inspection Request from: Rick Groom Inspection cancelled from web by: Rick Groom
|