Permit Number | FIR05-00339 |
Status | Finaled |
Name |
PROTEX
|
Site Address |
2590 N BOGUS BASIN RD
|
Project Name | alm - RIDLEYS FAMILY MARKET |
Customer Number | |
ePlanReview | |
Description |
To provide monitoring of the relocated cooking hood. Exiting zone #7 will be extended to the new hood location. No written comments, no functional matrix included in the package or FACP battery calculations. Applicant to provide FACP battery calculations based upon actual field measurements to the PDS Fire Inspector. The PDS Fire Inspector to field verify the activation of the cooking hood sends an alarm signal to the remote monitoring station and the batteries have sufficient capacity for the required 24 hours stand-by.
There is an associated cooking hood permit (FIR05-00307).
|