Permit Information
Permit NumberFIR05-00360
StatusFinaled
Name VIKING AUTOMATIC SPRINKLER CO
Site Address 403 S 11TH ST Unit: 320
Project NameSPR BRETT COMSTOCK-3RD FLR
Customer Number 
ePlanReview 
Description
(DR BRETT COMSTOCK)(11TH & MYRTLE-3RD FLR) To modify and existing shell fire sprinkler system installed under FIR05-00111, relocate and add fire sprinkler protection for the new 3,083-ft/2 medical office. Work will include shell sprinkler modification in Lease Space #310. This fire sprinkler work is related to the installation of new non-rated interior partitions, new suspended ceilings, and HVAC system. This building is fully fire sprinklered for area increase. This fire protection work shall comply with the IFC 2003 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD05-01543.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/24/200510/24/200510/24/2005PPASS
DetailsTroy Cobbley
Fire sprinklers finaled
INSP-Sprinkler Rough-in/Hydro10/5/200510/6/200510/6/2005APART
DetailsForrest France
Overhead sprinkler rough in is good for cover, one head at nw corner office is overspaced at approximately 200ft2 not meeting requirements of note #13 (calced spacing not to exceed 168ft2).