Permit Information
Permit NumberFIR05-00402
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 2476- 2482 N BOGUS BASIN RD
Project NameSPR HIGHLANDS VILLAGE BLD 10
Customer Number 
ePlanReview 
Description
HIGHLANDS VILLAGE BLD #10, HARRISON FLOOR PLAN TYPE * 2452, 2454, 2456 & 2458 N. Bogus Basin Rd. To install overhead fire sprinkler protection throughout a new 10,716-ft/2, three story, four unit apartment building. The first floor is 3,806-ft/2 which 2,000-ft/2 is for the garages (protected to Ordinary Group design), the second floor is 3,946-ft/2 and the third floor is 2,964-ft/2 (Light Hazard design). Three units are three bedroom and three and one half baths, one unit is four bedroom and three and one half baths. This building is fire sprinklered per NFPA 13-R. The fire sprinkler system work shall comply with the IFC 2000, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work. The underground fire service supply was installed under FIR04-00495. This permit is attached to building permit: BLD04-00944.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/14/20073/15/20073/15/2007APASS
DetailsForrest France
Final fire sprinkler inspection passed, noted missing escutcheons installed while on site.
INSP-Sprinkler Rough-in/Hydro3/13/20073/14/20073/14/2007PPART
DetailsForrest France
Overhead hydrostatic test completed satisfactory.
INSP-Sprinkler Rough-in/Hydro3/12/20073/13/20073/13/2007PNR
DetailsForrest France
Per phone call from contractor, system is not ready for inspection.
INSP-Sprinkler Rough-in/Hydro11/4/200611/6/200611/6/2006APART
DetailsForrest France
Repiped areas on the 3rd floor are acceptable, still need to complete tenting inspection prior to approval for cover.
INSP-Sprinkler Rough-in/Hydro11/2/200611/3/200611/3/2006APART
DetailsForrest France
Completed OH rough-in inspection for building 10, noted exposed 2" CPVC riser at 2nd floor to be concealed, three areas as noted on plans and indicated to contractor are subject to freeze potential and will require relocation of piping or approved tenting method prior to cover. 1st and 2nd floors only are approved for cover at this time, DP in the garage areas are not installed.
INSP-Sprinkler Rough-in/Hydro11/1/200611/2/200611/2/2006PCANC
DetailsForrest France
No time to complete this inspection.
FIR-Aging Inspection5/16/20065/16/20065/17/2006 DONE
DetailsForrest France
The building is currently still under construction, work in progress.