INSP-Final Inspection | 4/26/2006 | 4/26/2006 | 4/26/2006 | P | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Alarm Testing | 4/20/2006 | 4/26/2006 | 4/26/2006 | A | PASS |
Forrest France
|
|
|
Corrections have been completed, inspection passed.
|
INSP-Alarm Testing | 4/20/2006 | 4/20/2006 | 4/20/2006 | P | CANC |
Forrest France
|
|
|
Scheduled by a contractor via Hello! on 4/20/2006 at 10:07:34 AM. Contact: ###-####. To be completed early am at next scheduled inspection per conversation with contractor.
|
INSP-Alarm Testing | 4/10/2006 | 4/12/2006 | 4/12/2006 | A | FAIL |
Forrest France
|
|
|
The notification devices within the remodeled TI space failed to operate upon alarm activation under battery power.
|
INSP-Final Inspection | 10/20/2005 | 10/21/2005 | 10/21/2005 | A | PART |
Forrest France
|
|
|
Area notification devices tested satisfactory except in two areas which are not complete yet, will final when all devices have been installed and EOL is measured.
|
INSP-Final Inspection | 10/18/2005 | 10/19/2005 | 10/19/2005 | A | CANC |
Forrest France
|
|
|
Inspection to be scheduled for 10/21 a.m.
|
INSP-Final Inspection | 10/14/2005 | 10/18/2005 | 10/18/2005 | A | FAIL |
Forrest France
|
|
|
Horns and strobes must be synchronized as required by NFPA 72, notification in two areas is not installed yet due to remodel.
|
INSP-Final Inspection | 10/13/2005 | 10/14/2005 | 10/14/2005 | A | CANC |
Forrest France
|
|
|
mark; Phone #: ###-#### Cancel inspection per Mark due to scheduling conflict with the existing tenant for permission to alarm test, he will reschedule for next week.
|
INSP-Conference | 10/5/2005 | 10/6/2005 | 10/6/2005 | A | DONE |
Forrest France
|
|
|
On site discussion with Mark regarding completion of required work in phased projects, specifically two rooms which cannot be completed until the tenant moves to the newly remodeled area.
|
INSP-Conference | 10/4/2005 | 10/5/2005 | 10/5/2005 | A | DONE |
Forrest France
|
|
|
Conference has been rescheduled for thursday 10/6 per conversation with Mark M.
|