Permit Information
Permit NumberFIR05-00406
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 333 N 1ST ST
Project Namealm - ST LUKES
Customer Number 
ePlanReview 
Description
To provide total area notification in the TI space located on the first floor. A new NAC extender panel is being installed with the required smoke detector and a smoke detector is being installed over the exiting FACP.

The associated building permit (BLD 05-01557) is to remodel two existing tenant spaces to become one doctor's office of 5,323 sq. ft. per approved plans. Work includes selective demolition; infill of corridor door area with 1-hour construction to maintain 1-hour corridor rating; construction of new interior non-bearing, non-combustible walls to create office's, exam rooms, accessible restrooms, breakroom, reception, waiting and support areas; install suspended ceiling grid system within selected areas; upgrade electrical, mechanical, plumbing, sprinkler & alarm systems to meet tenant needs and minimum code compliance. (drs)) (ST LUKES-MEDICAL OFFICE PLAZA-1ST FLR)(MATERNAL FETAL MEDICINE) Building sprinklered for allowable area increase.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/26/20064/26/20064/26/2006PPASS
DetailsTroy Cobbley
permit finaled
INSP-Alarm Testing4/20/20064/26/20064/26/2006APASS
DetailsForrest France
Corrections have been completed, inspection passed.
INSP-Alarm Testing4/20/20064/20/20064/20/2006PCANC
DetailsForrest France
Scheduled by a contractor via Hello! on 4/20/2006 at 10:07:34 AM. Contact: ###-####. To be completed early am at next scheduled inspection per conversation with contractor.
INSP-Alarm Testing4/10/20064/12/20064/12/2006AFAIL
DetailsForrest France
The notification devices within the remodeled TI space failed to operate upon alarm activation under battery power.
INSP-Final Inspection10/20/200510/21/200510/21/2005APART
DetailsForrest France
Area notification devices tested satisfactory except in two areas which are not complete yet, will final when all devices have been installed and EOL is measured.
INSP-Final Inspection10/18/200510/19/200510/19/2005ACANC
DetailsForrest France
Inspection to be scheduled for 10/21 a.m.
INSP-Final Inspection10/14/200510/18/200510/18/2005AFAIL
DetailsForrest France
Horns and strobes must be synchronized as required by NFPA 72, notification in two areas is not installed yet due to remodel.
INSP-Final Inspection10/13/200510/14/200510/14/2005ACANC
DetailsForrest France
mark; Phone #: ###-#### Cancel inspection per Mark due to scheduling conflict with the existing tenant for permission to alarm test, he will reschedule for next week.
INSP-Conference10/5/200510/6/200510/6/2005ADONE
DetailsForrest France
On site discussion with Mark regarding completion of required work in phased projects, specifically two rooms which cannot be completed until the tenant moves to the newly remodeled area.
INSP-Conference10/4/200510/5/200510/5/2005ADONE
DetailsForrest France
Conference has been rescheduled for thursday 10/6 per conversation with Mark M.