Permit Information
Permit NumberFIR05-00427
StatusFinaled
Name GENERAL FIRE INC
Site Address 8904 W FAIRVIEW AVE
Project Name 
Customer Number 
ePlanReview 
Description
This permit is to upgrade an existing non UL 300 compliant cooking hood fire suppression sysem to UL 300 standards
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/18/20058/18/20058/18/2005PPASS
DetailsTroy Cobbley
Hood suppression systems operated correctly
INSP-Final Inspection8/16/20058/17/20058/17/2005PFAIL
DetailsTroy Cobbley
Of the two systems the suppression system over the griddle operated correctly. The suppression sytem over the fryers operated but the gas valve did not operate. Need to retest this and the manual pull as well as get documents for final.
INSP-Final Inspection8/16/20058/16/20058/16/2005PCANC
DetailsTroy Cobbley
Final Inspection of Ansul System; Phone #: ###-#### Internet Inspection Request from: Michael Heath Inspection cancelled from web by: Michael Heath