Permit Information
Permit NumberFIR05-00436
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 150 N CAPITOL BLVD
Project NameSPR CITY OF BOISE ANNEX
Customer Number 
ePlanReview 
Description
CITY OF BOISE ANEX * To replace and existing obsolete 4" dry pipe valve remove with a new Reliable Model F-1 dry pipe valve. The fire sprinkler system work shall comply with IFC 2003, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is not attached to a building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/29/20058/30/20058/30/2005APASS
DetailsForrest France
New dry pipe valve operated correctly, permit finaled.
INSP-Final Inspection8/16/20058/17/20058/17/2005AFAIL
DetailsForrest France
Need to coordinate trip test for new dry valve functionality verification.