Permit NumberFIR05-00447
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 2537 W STATE ST
Project NameSPR OH ST MARYS CROSSING BLDG1
Customer Number 
ePlanReview 
Description
ST MARY'S CROSSING BUILDING #1 (SHELL & CORE) - To install overhead light hazard occupancy, wet and dry piped systems in a new 16,870-ft/2, two story, wood frame office shell and core building. The core area will be finished under this permit including the three stairways and the lobby, elevator equipment room and mechanical/electrical room on the first floor. No occupancy is allowed under this permit. Separate tenant improvement permits will be required to finish this building for occupancy. The 1st floor is: 10,850-ft/2, the 2nd floor is: 6,020-ft/2. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. The underground fire service supply was permitted by the same contractor under FIR05-00355. This and the underground permit are attached to building permit: BLD05-0489.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/4/20061/5/20061/5/2006APASS
DetailsForrest France
Fire sprinkler passed final inspection.
INSP-Sprinkler Rough-in/Hydro1/3/20061/4/20061/4/2006APASS
DetailsTroy Cobbley
wet and dry system hydro tests passed
INSP-Sprinkler Rough-in/Hydro11/8/200511/8/200511/8/2005PPART
DetailsForrest France
Overhead sprinkler rough-in is acceptable.
INSP-Sprinkler Rough-in/Hydro10/24/200510/25/200510/25/2005PPASS
DetailsTroy Cobbley
24 hour hydro test passed. Sprinkler rough-in for the southwest dry system (area above insulation) passed.
INSP-Supply line flush10/18/200510/18/200510/18/2005PPART
DetailsForrest France
This inspection was for the associated UG permit FIR05-00355 to flush the supply line.
INSP-Sprinkler Rough-in/Hydro10/17/200510/17/200510/17/2005PPART
DetailsForrest France
Inspected outside soffit, concealed areas below stairs, hard lid areas 2nd floor, attic dry system 1st floor east and 2nd floor, provide coverage for concealed combustible mechanical shafts, provide restraint for sprig-ups over 4' in length.