Permit Information
Permit NumberFIR05-00448
StatusFinaled
Name COMMERCIAL FIRE PROTECTION
Site Address 1407 N MILWAUKEE ST
Project NameSPR DOLLAR TREE
Customer Number 
ePlanReview 
Description
(DOLLAR TREE) To remove, relocate and add fire sprinkler protection in an existing 14,772-ft/2 space to be used to a new retail sales tenant. The fire sprinkler work is related to new interior nonbearing walls, alterations to existing restrooms. This building is fire sprinklered for building area increase. This fire protection work shall comply with the IFC 2003 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD05-01748.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/26/20058/26/20058/26/2005PPASS
DetailsForrest France
Fire sprinkler permit finaled.
INSP-Final Inspection8/22/20058/23/20058/23/2005AFAIL
DetailsForrest France
Pendent head in womens restroom is blocked by a surface mounted light fixture, one head in the sales floor area is blocked by its proximity to a steel column, the remaining rough-in issues are acceptable.
INSP-Sprinkler Rough-in8/9/20058/9/20058/10/2005PPART
DetailsTroy Cobbley
Please call prior to inspection jeff; Phone #: ###-####
Rough-in is passed. Items that need corrected are uprights located along a north/south draft stop are spaced at 156 sq. ft. Contractor needs to provide verification that this spacing is approved. Also one upright head needs to be re-installed to correct an overspacing issue. See plans for location. The existing insulation that is installed on the underside of the roof deck is falling on the sprinkler piping and creating obstructions and needs repaired prior to installation of the ceiling tile. Annual inspection is needed and spare heads need to be placed in head box. Final spacing of pendants will be verified when t-bar and ceiling tile is installed. New hvac unit may create obstruction to uprights when installed and will need to be verified. Fire alarm panel is in trouble condition.
INSP-Conference7/29/20057/29/20057/29/2005PDONE
DetailsTroy Cobbley
###-#### jeff. Upright heads on both sides of beams to remain.