Permit Information
Permit NumberFIR05-00476
StatusFinaled
Name AUDIO ELECTRONICS INC
Site Address 12550 W EXPLORER DR
Project Namealm - Alpine Building
Customer Number 
ePlanReview 
Description
To provide a required manual fire alarm system that includes sprinkler monitoring, HVAC shutdown, elevator recall/shutdown and notification throughout.

The associated building permit (BLD 04-02346) is to construct a new 22,315 square foot, two story, concrete tilt-up office shell and core building and related site improvements. The core areas include restrooms and janitor's closets on the first and second floors, entry and hallways, mechanical room and elevator machine room on the first floor; elevator and stairways. This is a shell and core permit only and no occupancy is allowed under this permit. Separate tenant improvement permits will be required to finish this building for occupancy. The 2003 International Building Code, Section 1019, Exception #9 is being used as an alternate to the 2000 International Building Code, Section 1005.3.2 to allow two open stairways in a fully sprinklered building. All construction per the approved plans and attached comment list. (first floor 11,525,sq. ft., second floor 10,790 sq. ft.) #04-654/JCM Alpine Building (Shell & Core) -
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/12/20061/12/20061/12/2006PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection1/3/20061/4/20061/4/2006AFAIL
DetailsTroy Cobbley
zone 2 and 3 descriptions are not correct. need resubmitted plans
INSP-Final Inspection1/3/20061/3/20061/3/2006PFAIL
DetailsTroy Cobbley
Need resubmittals and the signals still are incorrect.
INSP-Final Inspection12/29/200512/30/200512/30/2005APART
DetailsTroy Cobbley
A temporary occupancy was given with Dave Hanneman's permission. Items needing addressing are syncing of the horns, mount map at facp, reverify signals (zone 10), and get the resubmitted plans approved.
INSP-Final Inspection12/27/200512/28/200512/29/2005AFAIL
DetailsTroy Cobbley
Resubmit plans showing the additional flow switch and tamper switch. Relocate the a/v's at the top of the stairs per the review comments and the approved plans. Test all elevator functions/recall. Provide map at the FACP. Remove the short tubes from the duct smoke detectors. Provide signal printout that the monitoring company received. Test all a/v's. Do inspection for the tenant improvement space. Provide minimum 8.3AH batteries for the FACP.
INSP-Sprinkler Rough-in/Hydro12/22/200512/23/200512/23/2005ACANC
DetailsTroy Cobbley
Canceled per Jason