Permit Number | FIR05-00563 |
Status | Finaled |
Name |
TREASURE VALLEY FIRE PROTECTION
|
Site Address |
308 S 24TH ST
|
Project Name | SPR VACANT COLLISION REP BOOTH |
Customer Number | |
ePlanReview | |
Description |
VACANT-COLLISION REPAIR CENTER * To remove an Extra Hazard sprinklered existing Spray Paint Booth and Prep Booth, sprinklers with Central GB, 3/4" thread 286ºF, 8.1 K-Factor fire sprinklers which included the exhaust plenums, filter banks, water wash tank, ducts (including the roof exhaust), installed under FIR99-00114 attached to building permit BLD99-00184. All piping and fire sprinklers will be removed up to an existing zone control valve, which means all items must be removed or sprinkler modifications will be required for existing protection to remain. The fire protection work shall be in accordance with minimum requirements of IFC-2003, and attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this permit, to provide witness of compliance verification of meeting minimum code. This permit is not attached to any building permit.
|