INSP-Final Inspection | 5/27/2010 | 5/27/2010 | 5/27/2010 | P | PASS |
Forrest France
|
|
|
Permit finaled.
|
FIR-Aging Inspection | 5/27/2010 | 5/27/2010 | 5/27/2010 | | DONE |
Forrest France
|
|
|
Final scheduled.
|
INSP-Final Inspection | 10/11/2005 | 10/12/2005 | 10/12/2005 | A | FAIL |
Forrest France
|
|
|
The hood suppression system operated correctly under test conditions. However, the manual pulls are obstructed from view and operation when the adjacent storage room door is in the fully open position- need to relocate pulls or provide automatic door closure as discussed. Also, two cooking burners on the 9 gallon system exceed the 4' limit to the hood edge, need to raise height so the cooking surface is within allowable limits.
|
INSP-Final Inspection | 10/10/2005 | 10/11/2005 | 10/11/2005 | A | FAIL |
Troy Cobbley
|
|
|
No test done since the fire alarm system was having problems for this end of the building and would not receive the hood alarm signal
|