Permit Information
Permit NumberFIR05-00576
StatusFinaled
Name PROTEX
Site Address 119 N 9TH ST
Project Namealm - PLAZA 121
Customer Number 
ePlanReview 
Description
Fire alarm permits FIR04-00657 and FIR04-00658 (shell and core) must be completed prior to occupancy for this permit (FIR05-00576).

To provide a new NAC extender panel, total notification, manual pull stations and three (3) duct smoke detectors and relay modules for HVAC shutdown to the new TI space located on in the basement and the first floor. The required manual fire alarm system includes sprinkler monitoring, HVAC shutdown, elevator recall/shutdown and notification throughout.

The associated building permit (BLD 05-00521) is to construct a restaurant tenant space on the 1st story (3,479 square feet) and in the basement (1,433 square feet) of an existing 6 story building. All public areas are located on the 1st story with a kitchen in the basement and a kitchen on the 1st story. Work is to include 2 restrooms accessible to the disabled, interior nonbearing walls, 3 grease hoods and ducts, millwork, suspended ceilings, and interior finishes. The work shall comply with the approved drawings, the plan review report, and all applicable codes. The fire sprinkler system shall comply with 2002 NFPA 13 as regulated by the Fire Department. Occupancy is NOT allowed until the plaza details have been completed per the Design Review. DRH03-230 **CJW** (ESTRELLA RESTAURANT - PLAZA 121 - BASEMENT AND 1ST FLR) This building is required to be fully fire sprinklered for several reasons.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/19/20064/19/20064/19/2006APASS
DetailsForrest France
The project related shell alarm permit has been completed, fire alarm finaled.
INSP-Final Inspection11/23/200511/25/200511/25/2005APART
DetailsForrest France
Fire alarm passed inspection, final pending shell alarm final.
INSP-Final Inspection11/23/200511/23/200511/23/2005PCANC
DetailsForrest France
This is my #. Please call me 20-30 minutes prior toy your arrival. Thanks, Grant; Phone #: ###-#### Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley
INSP-Final Inspection11/21/200511/22/200511/22/2005PPART
DetailsForrest France
Basement alarm tested okay, 1st floor testing not completed due to an AHU malfunction.
INSP-Conference10/28/200510/31/200510/31/2005ADONE
DetailsForrest France
On site discussion regarding duct smoke detector locations.
INSP-Conference10/27/200510/28/200510/28/2005PCANC
DetailsForrest France
this is Grants; Phone #: ###-#### Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley