Permit NumberFIR05-00616
StatusFinaled
Name HONEYWELL INC
Site Address 190 E BANNOCK ST
Project Namealm - ST LUKES-WEST WING
Customer Number 
ePlanReview 
Description
The original review (FIR01-00574; permit is expired) was to cover two fire alarm permit numbers, associated with two building permit numbers, being completed as one project. The project is to modify the existing manual and automatic hospital fire alarm system within both TI areas, with new initiating devices and strobes, connected to the existing fire alarm panel #10 which now serves floors B through 4 of this wing, on a new SLC circuit #2. The alarm system includes a manual alarm system, fire sprinkler system monitoring, corridor area smoke detection for release of smoke dampers penetrating corridor walls, induct detectors for release of smoke dampers in other wall, patient room smoke detectors and strobes. Strobes are to be connected to the existing NAC power extender panel connected to FACP #10. Audible alarms are provided by the existing paging system per prior agreement under FIR99-00596. Duct detectors for HVAC are reportedly existing and not included in these permits.

The building permit BLD 01-00843 (finaled 6/17/2005) was to remodel the North portion of the West Wing; area of remodel approximately 3,500 sq.ft. of north 1/2 of the 2nd floor for patient rooms & support areas. The floor for patient rooms, offices, and staff lounge. Work to include construction of interior non combustible, fire resistive walls; suspended ceiling grid system; electrical, mechanical, plumbing, sprinkler & alarm system upgrades; three (3) fully accessible patient room units; and interior finishes.

The building permit BLD 01-01632 is to remodel a 5,250 sq.ft. area on the south end of the floor for patient rooms, offices, and staff lounge per approved plans on file. Work to include construction of interior non-combustible, fire-resistive walls; suspended ceiling grid system; electrical, mechanical, plumbing, sprinkler & alarm system upgrades; three (3) fully accessible patient room units; and interior finishes. All per notes on plans and attached plan review comments, all part of the approved plans. NOTE: This building is fully sprinklered. A "LETTER OF COMPLETION / COMPLIANCE IS REQUIRED AS A CONDITION OF THIS PERMIT FOR OCCUPANCY OR USE OF THIS REMODELED FLOOR AREA. (P.C.#0499-01)/drs (ST LUKES-WEST WING)(SECOND FLOOR REMODEL-PHASE B)
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/23/20062/23/20062/23/2006PPASS
DetailsForrest France
Fire alarm finaled.
INSP-Alarm Testing2/22/20062/23/20062/23/2006APASS
DetailsForrest France
c/n items have been completed as requested, changes are indicated on as-built drawings.
INSP-Final Inspection2/20/20062/22/20062/22/2006AFAIL
DetailsForrest France
Two storage rooms and one housekeeping room will require smoke detection, relocate one strobe in the staff lounge to provide full coverage, add missing strobe in the locker room, provide visual notification for the work station adjacent to the corridor.