Description |
The original review (FIR01-00574; permit is expired) was to cover two fire alarm permit numbers, associated with two building permit numbers, being completed as one project. The project is to modify the existing manual and automatic hospital fire alarm system within both TI areas, with new initiating devices and strobes, connected to the existing fire alarm panel #10 which now serves floors B through 4 of this wing, on a new SLC circuit #2. The alarm system includes a manual alarm system, fire sprinkler system monitoring, corridor area smoke detection for release of smoke dampers penetrating corridor walls, induct detectors for release of smoke dampers in other wall, patient room smoke detectors and strobes. Strobes are to be connected to the existing NAC power extender panel connected to FACP #10. Audible alarms are provided by the existing paging system per prior agreement under FIR99-00596. Duct detectors for HVAC are reportedly existing and not included in these permits.
The building permit BLD 01-00843 (finaled 6/17/2005) was to remodel the North portion of the West Wing; area of remodel approximately 3,500 sq.ft. of north 1/2 of the 2nd floor for patient rooms & support areas. The floor for patient rooms, offices, and staff lounge. Work to include construction of interior non combustible, fire resistive walls; suspended ceiling grid system; electrical, mechanical, plumbing, sprinkler & alarm system upgrades; three (3) fully accessible patient room units; and interior finishes.
The building permit BLD 01-01632 is to remodel a 5,250 sq.ft. area on the south end of the floor for patient rooms, offices, and staff lounge per approved plans on file. Work to include construction of interior non-combustible, fire-resistive walls; suspended ceiling grid system; electrical, mechanical, plumbing, sprinkler & alarm system upgrades; three (3) fully accessible patient room units; and interior finishes. All per notes on plans and attached plan review comments, all part of the approved plans. NOTE: This building is fully sprinklered. A "LETTER OF COMPLETION / COMPLIANCE IS REQUIRED AS A CONDITION OF THIS PERMIT FOR OCCUPANCY OR USE OF THIS REMODELED FLOOR AREA. (P.C.#0499-01)/drs (ST LUKES-WEST WING)(SECOND FLOOR REMODEL-PHASE B)
|