Permit Information
Permit NumberFIR05-00698
StatusFinaled
Name ALARMCO
Site Address 101 N 10TH ST
Project Namealm - GEM NOBLE BLDG
Customer Number 
ePlanReview 
Description
The data has been moved to a Word document attached to this case.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Alarm Testing7/13/20097/14/20097/14/2009APASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection7/14/20097/14/20097/14/2009PPASS
DetailsTroy Cobbley
permit finaled
INSP-Alarm Testing7/10/20097/13/20097/13/2009AFAIL
DetailsTroy Cobbley
An additional strobe needs to be added in an alcove in the first floor electrical room and almost all of the horn/strobes on the second floor, in the residential rooms did not operated. Per Guy it appears that the notification circuit had been damaged. The map needs to be provided at the annunciator.
INSP-Final Inspection7/9/20097/10/20097/10/2009APART
DetailsForrest France
Fire alarm testing completed satisfactory today includes the FACP, nac panels, remote annunciator, elevator recall functions, mag locks at exit doors, signals sent to remote station, all initiating devices and sprinkler monitoring per new plan resubmittals. Items needed for final include retest the non-functional duct detector at the roof, provide correct addressing at three smoke detectors, repair one MP and replace one h/s on the first floor, provide a map at the annunciator, show locations of hoistway sd and hd on the site map, verifiy functionality of notification appliances throughout.
INSP-Final Inspection6/24/20096/25/20096/25/2009ANR
DetailsForrest France
Need to provide approved plan resubmittals indicating field modifications and changes to system installation which differ significantly from the original design. Also need to coordinate field acceptance testing with the fire sprinkler contractor for system interconnections.
INSP-Final Inspection6/3/20096/4/20096/5/2009PFAIL
DetailsForrest France
Building walkthrough completed for scope of fire alarm permit work, noted several areas on plans in need of adjustment, repair, provision or modification. Some items such as elevator recall are not ready for testing. Missing relays for mag locks at two main entry doors, MP stations at the west open area are not yet installed, plans need to reflect field installation including actual number of nac panels/circuts, added sprinkler monitor points at floor control manifolds, new relays, added devices etc. See stamped drawings for red-lined annotations.
FIR-Aging Inspection8/15/20068/15/20068/15/2006 DONE
DetailsForrest France
wip