Permit Information
Permit NumberFIR05-00726
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 794 W BROAD ST
Project NameTULLY'S BODO 7 SPR
Customer Number 
ePlanReview 
Description
(TULLY'S - BODO BLDG #7 - 1ST STORY) This building is fire sprinklered for fire area and to allow the multitheater complex. To install fire sprinklers in the creation of a new 1,252-ft/2 retail sales tenant space within a new 135,950-ft/2 building, located on the 1st story, on the West side of the building. Fire sprinkler work is related to new interior nonbearing walls, two restrooms and suspended and hard lid ceilings. This building is required to be fully fire sprinklered. This fire protection work shall comply with the IFC 2003 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. The shell permit is: FIR05-00372. This permit is attached to building permit: BLD05-02432.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/21/20073/22/20073/22/2007APASS
DetailsForrest France
Fire sprinkler permit finaled.
INSP-Final Inspection11/15/200511/16/200511/16/2005PPART
DetailsForrest France
Overhead sprinkler work is complete and satisfactory, final pending shell sprinker final approval.
INSP-Sprinkler Rough-in11/4/200511/7/200511/7/2005AFAIL
DetailsForrest France
Attatch retaining strap at beam clamp on arm-over hanger, heads within one foot of heat diffusers must be intermediate temperature, heads in the drop ceiling areas are not cut in at this time.