Description |
Fire alarm permit FIR05-00169 (shell and core) must be completed (finaled) prior to occupancy for permit (FIR05-00735).
Fire alarm permit FIR05-00169 (shell and core) and FIR05-00715 (pre-action releasing system) must be completed (finaled) prior to occupancy for permit (FIR05-00734).
To provide total notification, fire/smoke damper control and HVAC shutdown to an existing required manual fire alarm system which includes, manual fire boxes, HVAC shutdown, fire/smoke damper control, elevator recall/shutdown and total notification throughout.
FIR05-00715 is a pre-action releasing system (panel located in the electrical room, first floor) that will supply an IT room on the second floor and the electrical room (first floor directly below the IT room) that feeds the IT room. The FACP shall monitor the pre-action control panel for alarm, supervisory and trouble signals.
FIR05-00734 is associated with building permit BLD05-01478 is to occupy the entire second floor in existing vacant shell building per approved plans. Work under this permit will also include constructing a building core corridor with lobby, exercise room with showers, pantry, mail room, and janitor's closet on the first floor of the building. Work to include new interior walls, new interior doors, some new interior glazing, interior finish, new suspended ceiling installation, new soffit work, new cabinets/counters and sinks, fire sprinkler and fire alarm work, new mechanical, new plumbing, and new electrical work. A Certificate of Occupancy is to be issued when completed and approved. NOTE: This building is fully fire sprinklered for story increase and area increase. JCB (CLICKSALES)(KEYNETICS BLDG - 2ND FLOOR) New 7,628 sq. ft. office tenant
FIR05-00735 is associated with building permit BLD05-01480 is to occupy the entire third floor in existing vacant shell building per approved plans. Work to include new interior walls, new interior doors, some new interior glazing, interior finish, new suspended ceiling installation, new soffit work, new cabinets/counters and sinks, fire sprinkler and fire alarm work, new mechanical, new plumbing, and new electrical work. A Certificate of Occupancy is to be issued when completed and approved. NOTE: This building is fully fire sprinklered for story increase and area increase. JCB (KEYNETICS)(KEYNETICS BLDG - 3RD FLOOR) New 7,967 sq. ft. office tenant
|