Permit NumberFIR05-00739
StatusFinaled
Name CM COMPANY
Site Address 5959 N DISCOVERY PL
Project NameSPR W. BOISE YMCA 2ND STORY AD
Customer Number 
ePlanReview 
Description
(WEST BOISE FAMILY YMCA - SECOND STORY ADDITION) This building is fire sprinklered for building area increase. Demolition is covered under permit FIR05-00569 under BLD05-02313. To install 34 sprinklers beneath and 23 dropped sprinklers in the second level for a 2,800-ft/2, 2nd story addition within an existing recreational facility. Fire sprinkler work is related to the new mezzanine constructed of steel columns, steel beams, concrete floor, and new suspended ceilings. This fire protection work shall comply with the IFC 2003 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD05-01564.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/13/200512/14/200512/14/2005APASS
DetailsTroy Cobbley
Permit finaled.
INSP-Final Inspection12/8/200512/9/200512/9/2005AFAIL
DetailsTroy Cobbley
First floor area is missing canopys and on e head is painted. Need access to verify connection. Second floor piping is ok to cover.
INSP-Sprinkler Rough-in/Hydro11/17/200511/17/200511/17/2005PPART
DetailsTroy Cobbley
First floor hydro test and rough-in passed.