INSP-Final Inspection | 7/14/2009 | 7/15/2009 | 7/14/2009 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled per requirement of last inspection entry. Notification coverage verified.
|
INSP-Final Inspection | 7/9/2009 | 7/10/2009 | 7/10/2009 | A | PART |
Forrest France
|
|
|
Initiating device testing passed, final pending notification appliance testing for one relocated 110cd strobe at the dining area per resubmitted plans.
|
INSP-Final Inspection | 6/13/2007 | 6/15/2007 | 6/15/2007 | A | PART |
Forrest France
|
|
|
Duct detectors need to initiate a supervisory signal, not alarm as currently programed, the remainder of tenant fire alarm work passed inspection, a shelf in the mech. room blocking strobe coverage removed while on site.
|
INSP-Final Inspection | 6/5/2007 | 6/7/2007 | 6/7/2007 | A | NR |
Forrest France
|
|
|
Pending hood suppression tie in.
|
FIR-Aging Inspection | 9/4/2006 | 9/4/2006 | 9/5/2006 | | DONE |
Forrest France
|
|
|
wip
|