Permit Information
Permit NumberFIR05-00771
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 11427 W EXECUTIVE DR
Project NameSPR OH SILVER CREEK SUPPLY
Customer Number 
ePlanReview 
Description
SILVER CREEK SUPPLY - To install a complete OH-2 wet and dry overhead fire sprinkler system in a new 27,500-ft/2, two story pre-engineered metal building and wood interior framed retail, office and warehouse building. This building is fully fire sprinklered for area increase. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. The underground supply was permitted separately under FIR05-00731. Both this and the underground permits are attached to building permit: BLD05-02319.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/16/20063/17/20063/17/2006APASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection3/16/20063/16/20063/16/2006PFAIL
DetailsTroy Cobbley
Need pressure relief installed on the wet system and revised calcs
INSP-Sprinkler Rough-in/Hydro3/14/20063/14/20063/14/2006PPASS
DetailsTroy Cobbley
24 hour air test passed
INSP-Sprinkler Rough-in/Hydro3/13/20063/13/20063/13/2006PPASS
DetailsTroy Cobbley
24 hour air test on the dry system started at 12:50 with 44psi on guage.
INSP-Sprinkler Rough-in/Hydro3/10/20063/10/20063/10/2006 PASS
DetailsTroy Cobbley
Wet system hydro test passed. Need copy of the test papers.
INSP-Sprinkler Rough-in/Hydro3/8/20063/9/20063/9/2006APART
DetailsTroy Cobbley
200lb. hydro test for the dry system passed. Hydro test for the wet system failed. Also still need the fdc installed and hydro tested.
INSP-Sprinkler Rough-in/Hydro3/7/20063/8/20063/8/2006ACANC
Steve ###-####///3-8-06 Cancel because forgot to enter Assigned inspector and insp didn't register eus
INSP-Sprinkler Rough-in/Hydro1/20/20061/23/20061/23/2006APART
DetailsTroy Cobbley
Restrooms as marked on the approved plans are ok to cover