Permit Information
Permit NumberFIR05-00825
StatusFinaled
Name AUDIO ELECTRONICS INC
Site Address 12550 W EXPLORER DR Unit: 200
Project Namealm - ALPINE BLDG-2ND FLR
Customer Number 
ePlanReview 
Description
The shell and core fire alarm permit (FIR05-00476) must be finaled prior to occupancy for this fire alarm permit. This permit is to provide total notification coverage in the TI space on the 2nd floor (STE 200). The required manual fire alarm system includes sprinkler monitoring, HVAC shutdown, elevator recall/shutdown and notification throughout.

The building permit BLD05-01604 is to construct a 6,322 sq.ft. office tenant located on the second floor, in a new shell building per approved plans. The shell & core was permitted under Bld04-02346. Work to include, construction of new interior partitions, installation of suspended ceiling system and related lighting, connect to existing HVAC system and install new ducting and registers, Miscellaneous related interior finishes counters and cabinets. This building is fully fire sprinklered any alterations to the sprinkler system shall be per NFPA #13 as regulated by the fire department. (Rmh)- (ALPINE REAL ESTATE LLP)(ALPINE BLDG-STE 200)
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/12/20061/12/20061/12/2006PPASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection1/3/20061/4/20061/4/2006AFAIL
DetailsTroy Cobbley
zone 2 and 3 descriptions are not correct. need resubmitted plans
INSP-Final Inspection1/3/20061/3/20061/3/2006PFAIL
DetailsTroy Cobbley
Need resubmittals and the signals still are incorrect.
INSP-Final Inspection12/29/200512/30/200512/30/2005APART
DetailsTroy Cobbley
A temporary occupancy was given with Dave Hanneman's permission. Items needing addressing are syncing of the horns, mount map at facp, reverify signals (zone 10), and get the resubmitted plans approved.
INSP-Final Inspection12/27/200512/28/200512/29/2005AFAIL
DetailsTroy Cobbley
Need to test the a/v's. Remove short tubes from the duct smoke detectors. Final shell permit.
INSP-Final Inspection12/22/200512/23/200512/23/2005ACANC
DetailsTroy Cobbley
Canceled per Jason