Permit Information
Permit NumberFIR06-00007
StatusFinaled
Name MICRON TECHNOLOGY INC FA
Site Address 8000 S FEDERAL WAY
Project Namealm -
Customer NumberC9051
ePlanReview 
Description
Fire Alarm System: C9051 The existing Pyrotronics fire alarm control panel will be replaced with a new Edwards control panel. All associated initiating devices will also be replaced with Edwards devices. However, the existing Pyrotronics System 3 horn panel will remain, along with the notification appliances. The entire building will be brought up to code in the process.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/30/200710/31/200711/1/2007APASS
DetailsForrest France
Fire alarm final inspection passed, permit finaled.
INSP-Final Inspection10/25/200710/26/200710/26/2007APART
DetailsForrest France
Tested remainder of the second floor devices, noted two SD installed too close to HVAC registers, door hardware at the inactive leaf at the west set of fire doors to the skybridge is not approved, corrections from the previous inspection are complete.
INSP-Final Inspection10/23/200710/25/200710/25/2007ADEFR
DetailsForrest France
Scheduled for 10/26
INSP-Final Inspection10/16/200710/17/200710/17/2007ACANC
DetailsTroy Cobbley
Cancell per Jeff Walton
INSP-Final Inspection10/3/200710/4/200710/4/2007APART
DetailsForrest France
See plans for areas tested on the second floor, noted items in need of correction, HD at the elevator machine room tested okay.
INSP-Final Inspection8/23/20078/24/20078/24/2007APART
DetailsForrest France
1st floor fire alarm testing completed today, items remaining for the 1st floor include lacking HD at the elevator machine room and missing main FACP door.
INSP-Final Inspection8/21/20078/23/20078/23/2007ACANC
DetailsForrest France
No time available to complete this inspection today, rescheduled for 8/24 AM as agreed.
INSP-Final Inspection8/14/20078/16/20078/16/2007APART
DetailsForrest France
Retested items on the first floor in need of correction, doors need adjusted at the service elevator lobby, missing a HD for the elevator machine room, two SD at the link relocated while on site, several items remain to be tested at the 2nd floor.
INSP-Final Inspection8/7/20078/9/20078/9/2007ADEFR
DetailsForrest France
No time to complete this inspection today, rescheduled as discussed.
INSP-Alarm Testing6/27/20076/29/20077/2/2007AFAIL
DetailsForrest France
SD's as installed in the electrical room, comm. room, and loading dock area do not meet spacing requirements due to structural beam blockage, missing one SD at a vestibule, visible notification is blocked at some areas in the pyro lab, duct detectors and vesdas tested okay on the first floor, noted corrections from the previous visit have been completed.
INSP-Sprinkler Rough-in/Hydro6/8/20076/13/20076/13/2007APART
DetailsForrest France
Tested a/v notification in the cleanroom areas-noted lacking coverage and overspaced devices at some locations, tested FACP batteries, AC loss, smoke at panel, manual pull stations for the basement and 1st floor tested okay, verified corrections at the basement from previous visit.
INSP-Final Inspection6/6/20076/7/20076/7/2007ACANC
DetailsForrest France
No time available for this inspection today.
INSP-Final Inspection6/5/20076/6/20076/6/2007ACANC
DetailsTroy Cobbley
Forrest, pls call when on your way. JB needs about a 30 min notice. Phone #: ###-#### Internet Inspection Request from: Rob Puckett Inspection cancelled from web by: Rob Puckett
INSP-Alarm Testing5/29/20075/31/20075/31/2007APART
DetailsForrest France
Walk through testing of a/v notification at the 1st , 2nd and basement floor levels only completed today, noted one horn to be replaced in the basement, some areas on the first and second floors appear to be overspaced or obstructed as noted, as-built plans need to accurately reflect locations of all devices, the 1st floor pyro room may need an additional horn, clean room areas on the 1st floor remain to be verified for a/v testing due to access issues, audibility and synchronization throughout the remainder of the project are acceptable.
FIR-Aging Inspection10/30/200610/30/200610/31/2006 DEFR