Permit Information
Permit NumberFIR06-00008
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 4601 S SURPRISE WAY
Project NameSPR TRINITY PRESBYTERIAN CH
Customer Number 
ePlanReview 
Description
TRINITY PRESBYTERIAN CHURCH * To remove 6 upright Tyco Series "EC-11", SSU, 11.2 K-factor, (¾"), TY5137 with Tyco Series "EC-11", SSP, 11.2 K-factor, (¾"), TY5237 in a Youth Activity Room #160 due to the installation of a new dropped ceiling system. The overhead fire sprinkler work shall comply with the IFC 20003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD04-01909.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/27/20105/27/20105/27/2010PPASS
DetailsForrest France
Project verified for completion, c/n items finished, aging fire sprinkler permit final okay.
FIR-Aging Inspection5/27/20105/27/20105/27/2010 DONE
DetailsForrest France
Site visit scheduled.
INSP-Sprinkler Rough-in1/12/20061/12/20061/12/2006PPART
DetailsForrest France
Overhead rough-in is acceptable for cover. No final until all ceiling tile and escutcheons are installed to facilitate heat collection and maintain the listing for the heads.