INSP-Final Inspection | 1/31/2006 | 2/1/2006 | 2/1/2006 | A | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Final Inspection | 1/30/2006 | 1/31/2006 | 1/31/2006 | A | FAIL |
Forrest France
|
|
|
The cooking surface of one appliance exceeds 4' to the hood lip, nozzles at the smaller hood system failed to discharge during testing. Gas and power did shut down at both hoods during the test.
|
INSP-Final Inspection | 1/24/2006 | 1/25/2006 | 1/25/2006 | P | CANC |
Troy Cobbley
|
|
|
Appliances are missing. No inspection performed.
|