Permit NumberFIR06-00051
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 3157 S BOWN WAY
Project NameSPR DR TIM HUFF
Customer Number 
ePlanReview 
Description
DR. TIM HUFF-BOWN CROSSING * This building is NOT fire sprinklered. To install fire sprinkler protection in a medical gas storage closet per the IFC Chapter 3006 and the Fire Department published policy for protection for the same within a new 5,800-ft/2, one-story, multi tenant, office building. The first floor is 5,177-ft/2 and the second floor is 623-ft/2. The center section is being finished under this permit and will be occupied as a dentist office. The fire sprinkler system work shall comply with these conditions, the IFC 2003 Edition, the attached review comments, as regulated by the Fire Chief. The review notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD05-02927.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/18/20064/19/20064/19/2006APASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection4/18/20064/18/20064/18/2006PFAIL
DetailsForrest France
Provide lockable supervision for the valves at the backflow prevention device, provide signage per fire code review notes at the BPD, the dry sidewall is installed in such a manner that does not prevent freezing of the supply pipe.
INSP-Final Inspection4/14/20064/17/20064/17/2006ACANC
DetailsTroy Cobbley
contractor had not done work yet