INSP-Final Inspection | 2/27/2007 | 3/2/2007 | 3/2/2007 | P | PASS |
Forrest France
|
|
|
Final fire sprinkler inspection passed, flow switch delay adjusted while on site, permit finaled.
|
INSP-Sprinkler Rough-in/Hydro | 2/27/2007 | 3/2/2007 | 3/2/2007 | A | PART |
Forrest France
|
|
|
OH hydrostatic test passed. The OH rough-in installation is satisfactory, noted missing test orfice at remote inspectors test connection.
|
INSP-Sprinkler Rough-in/Hydro | 3/31/2006 | 4/4/2006 | 4/4/2006 | A | CANC |
Forrest France
|
|
|
Scheduled by a contractor via Hello! on 3/31/2006 at 1:34:47 PM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Apr 4 2006 7:17AM.
|
INSP-Supply line flush | 3/31/2006 | 4/3/2006 | 4/3/2006 | A | PART |
Forrest France
|
|
|
UG fire supply line flush performed satisfactory.
|
INSP-Sprinkler Rough-in/Hydro | 3/28/2006 | 3/28/2006 | 3/28/2006 | A | PART |
Forrest France
|
|
|
UG supply line hydrostatic test inspection passed.
|
INSP-Supply line flush | 3/21/2006 | 3/23/2006 | 3/23/2006 | P | PART |
Forrest France
|
|
|
UG fire supply line has been relocated to attain the proper depth of bury as required, thrust blocking verified, UG is okay to cover.
|
INSP-Supply line flush | 3/17/2006 | 3/20/2006 | 3/20/2006 | P | FAIL |
Forrest France
|
|
|
Inspection was for UG supply line cover. Depth of bury for the entire pipe run does not meet the required 4'-6" to top of pipe for this locality (the actual install is approximately 3'-6" from top of pipe to floor slab at the building and 3'-6" to 4'-0" to grade for the remainder).
|