Permit Information
Permit NumberFIR06-00098
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 1055 N CURTIS RD
Project NameSPR ST AL'S CNTRL TWR 1ST FL P
Customer Number 
ePlanReview 
Description
(ST ALPHONSUS CENTRAL TOWER - 1ST FLOOR PHARMACY) To modify existing 4" FDC main, a 2½" wet main off the S. Tower System #1 and area sprinkler branch lines. The two mains are being raised over the chiller piping, two branch lines are being relocated and one new branch line is being installed. Hazard is Ordinary Group 1 with 130-ft/2 maximum spacing. The existing pipe schedule system was installed in 1969 by Interstate Fire and remodeled by TVFP in 1991. Mains are currently looped, fed by a fire pump. This work is not located in a hydraulic calculated area. No other fire sprinkler work is addressed in this permit. Fire sprinkler work shall be in accordance with minimum requirements of IFC-2003, and attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this permit, to provide witness of compliance verification of meeting minimum code. This permit is attached to BLD05-00635.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/12/200612/12/200612/12/2006PPASS
DetailsTroy Cobbley
permit finaled
INSP-Sprinkler Rough-in2/16/20062/16/20062/16/2006PPASS
DetailsTroy Cobbley
Permit finaled